Tripp Lite PDUMH30HVATNET 5.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V L6-30P Inputs, 16-C13 2-C19 & 1 L6-30R Outlet, 2U, TAA

product id: 101112

Category: Electronic Production Supplies, Power Management

Manufacturer: Tripp Lite

InstruHub is a leading supplier and reseller of Tripp Lite Electronic Production Supplies, Power Management in Russia, and we ship to all major cities such as Moscow


  • Single phase 24A 200-240V Auto Transfer Switch / ATS PDU with Solid State Switching
  • Separate primary & secondary inputs enable redundant-power option for non-redundant network devices
  • Pre-installed WEBCARDLX with latest version of PADM20 for IP-based Auto Probe feature
  • 2U rackmount, 2 L6-30P inputs, 19 switched outlets (16 C13, 2 C19, 1 L6-30R)
  • Individually switched outlets, network interface and visual current, voltage and environmental monitoring


•200-240V 30A Automatic Transfer Switch (ATS) / Switched PDU (Agency de-rated to 24A continuous)
•ATS features provide redundant power for critical network equipment with a single input power cord
•2 digit display reports output power consumption in amps
•2U horizontal rackmount form factor; 12.5 in. / 31.8 cm depth
•19 built-in switched outlets (16 C13, 2 C19 & 1 L6-30R)
•Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
•Set of two 10-ft. / (3.05 m) NEMA L6-30P input cables support connection to separate PRIMARY and SECONDARY inputs
•ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails or becomes unstable, the ATS will switch to maintain output sourced from the secondary input cable until power on the primary input is restored and stable
•ATS configurations enable fault-tolerant, hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time similar to Tripp Lite SmartOnline series)
•Advanced ATS configurations utilizing separate mains circuits, backup generators and even separate out of phase utility power grid feeds are fully supported
•On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the primary source
•Super-fast switch-over between primary and secondary power sources occurs in 2-6 milliseconds
•Switched outlets and Ethernet interface supports individual outlet control on a real-time or programmable basis and user-specified alarm notification thresholds for all reported site power conditions
•Pre-installed WEBCARDLX with the latest version of PowerAlert Device Manager firmware (PADM20) provides enhanced remote management capabilities
•PADM20 and PowerAlert Element Manager (PAEM) form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations
•IP-based Auto Probe detects lost connectivity and restores service autonomously
•Outlets are factory programmed for sequential turn-on at 250 millisecond intervals when the PDU is first energized to prevent inrush-related equipment interaction on startup
•Front panel LED's confirm power availability on both input lines and for each output receptacle
•Includes IEC plug retention sleeves to keep vital network equipment plugged in and continuously powered
•Compliant with the Federal Trade Agreements Act (TAA) for GSA Schedule purchases

Includes 2U PDUMH30HVATNET 24A ATS SWITCHED PDU, 2U rackmount installation brackets, (16) IEC C13 plug retention sleeves, (2) IEC C19 plug retention sleeves , (1) Micro-USB-to-USB A configuration cable (73-1689), User manual
Type PDU
Note Batteries not Required to Operate
Warranty Information 2-year limited warranty

Why Buy from InstruHub:




Similar products

call
phone whatsApp mail